Last Updated on October 27, 2023 by Electricalvolt
Current transformers are used for measurement of electrical parameters like ampere, power, and energy. CTs are also used for measuring the current at fault condition and tripping of the upstream breaker to avoid damage to the electrical network. From the perspective of the protection of the electrical network, the current transformer accuracy class is significant, and it plays a vital role in ensuring the security of the electrical network.
There are three types of current transformers.
- Metering Class CT
- Protection Class CT
- Special Protection Class CT
Metering Class CT
The metering class CT is used for the measurement of electrical parameters. The crucial role of CT is that it should measure the current accurately without much error. The accuracy class parameter is very important for metering CT. The following specifications need to be checked for the metering class current transformer.
Important Parameters of Metering Class CT
CT Ratio
The current transformation ratio(CTR) is defined as the ratio of the input current to the output current. The current transformer of 300/5 CTR means if the primary current is 300 Amp, then the secondary current is 5 Amp.
CT Burden
The burden of the current transformer is expressed in VA. The total total burden should be taken into account when CT is used for measuring or protection purposes. To calculate the total burden of the secondary circuit of the CT, the total resistance of the secondary side of the CT should be considered. The secondary winding of CT is connected to the measuring equipment or protection circuit through pilot wires. The total resistance of the secondary circuit is the sum of CT secondary winding resistance, connecting wires resistance, and the resistance of the relay/meter.
Example
If the relay resistance is 0.1 ohm, the connecting wire resistance is 0.2 ohm, and the secondary winding resistance of CT is 0.1 ohm. The total resistance of the secondary circuit is 0.1+0.2+0.1= 0.4 ohm. If the rated secondary current of the CT is 5 Amp, then the secondary voltage is (Is*Rburden)= 0.4*5=2 volts. The burden of the current transformer is =Is*Vs= 5*2= 10 VA.
Rating Factor
Multiples of Rated Current to which the CT can maintain its accuracy is called the rating factor of CT. Typical rating factor is 1, 1.5, 2, 3, 4. Example: 500/5A CT with RF 2 CT will maintain its accuracy certification up to 1000A.
CT Class
The standard accuracy classes, according to IEC, are classes 0.2, 0.5, 1, 3, and 5. The CT with accuracy classes of 0.1, 0.2, 0.5, and 1.0 are used for the measurement of electric current. 0.1 and 0.2 accuracy class CT are used in a revenue metering application. 0.2 class metering CT means the CT functions within the specified accuracy limit at 100 % and 120 % of the rated CT current, and the accuracy limit error is 0.2 %. The CT operates in the linearity zone of the magnetization curve, and it consumes a very low magnetizing current. The 0.3 class CT reads 0.993 to 1.003 at 100% rated current, and at 10% current, the CT reads in the range of 0.994 to 1.006.
The core of metering CT gets saturated when the current above its rated current flows through it. The current is limited within the device. This protects the connected metering device from overloading in case of the fault current. The salient features of metering CT are as follows.
- High accuracy in a smaller range
- Less core material is required
- This leads to lower saturation voltages
The metering CT has less core material compared to the core material of the protection class CT. The metering CT specification is written in the form of 0.3 B 1.8. The first number is the current transformer accuracy class, B stands for the metering class, and 1.8 is the maximum burden that can be connected to the CT.
0.2s and 0.5s class CT are used in revenue metering applications. The 0.2 s and 0.5s class CT have a ratio error of 0.2 % for current from 20 to 120% of the rated current.
The ratio and phase angle error for measuring the current transformer of 0.2s -0.5s class are given below.
Accuracy Class
|
±Percentage Current (Ratio) Error at Percentage of Rated Current Shown Below
|
±Phase Displacement at Percentage of Rated Current Shown Below
|
|||||||||||||||
Minutes
|
Centiradians
|
||||||||||||||||
1
|
5
|
20
|
100
|
120
|
1
|
5
|
20
|
100
|
120
|
1
|
5
|
20
|
100
|
120
|
|||
0.2S
|
0.75
|
0.35
|
0.2
|
0.2
|
0.2
|
30
|
15
|
10
|
10
|
10
|
0.9
|
0.45
|
0.3
|
0.3
|
0.3
|
||
0.5S
|
1.5
|
0.75
|
0.5
|
0.5
|
0.5
|
90
|
45
|
30
|
30
|
30
|
2.7
|
1.35
|
0.9
|
0.9
|
0.9
|
The ratio and phase angle error for measuring current transformer of 0.1 -1.0 class are as given below.
Accuracy Class
|
±Percentage Current (Ratio) Error at Percentage of Rated Current Shown Below
|
±Phase Displacement at Percentage of Rated Current Shown Below
|
||||||||||
Minutes
|
Centiradians
|
|||||||||||
5
|
20
|
100
|
120
|
5
|
20
|
100
|
120
|
5
|
20
|
100
|
120
|
|
0.1
|
0.4
|
0.2
|
0.1
|
0.1
|
15
|
8
|
5
|
5
|
0.45
|
0.24
|
0.15
|
0.15
|
0.2
|
0.75
|
0.35
|
0.2
|
0.2
|
30
|
15
|
10
|
10
|
0.9
|
0.45
|
0.30
|
0.30
|
0.5
|
1.50
|
1.75
|
0.5
|
0.5
|
90
|
45
|
30
|
30
|
2.7
|
1.35
|
0.9
|
0.9
|
1.0
|
3.0
|
1.5
|
1.0
|
1.0
|
180
|
90
|
60
|
60
|
5.4
|
2.7
|
1.8
|
1.8
|
Protection Class CT
Protection class CT is connected to the protection relay that gives a tripping command to the circuit breaker at the time of fault condition. The protection class CT has the following features.
- CT is required to perform in fault current
- Moderate accuracy over a broader range
- More core material is needed
At the time of fault, the primary current of CT increases abnormally high and the core can get magnetized above its rated capacity, and whatever fault current flowing in the circuit can’t be reflected in the secondary side of the CT. This phenomenon is known as the saturation of CT. If CT gets saturated at the time of the fault, the protection relay will not operate.
According to IEEE C57.13-2008, C200 CT has the following specifications.
Example:
5P10 class CT
If the primary current is 10 times the rated primary current of the CT, the CT will function perfectly within the accuracy limit of 5 %. A 5P20 CT has an Accuracy limit of 5% at 20 times rated current (Accuracy Limit Factor). The accuracy class of the current transformer of this CT at rated current is 1%.
Marking on CT
- 10VA5P10
- 15VA10P10
- 30VA5P20
Protection Special(PS) class CT
- Knee Point Voltage of CT
- Burden of CT
- Difference between 0.2 and 0.2S class Metering CT
- 5P20 Class Protection CT
- Accuracy Limit Factor(ALF) of CT
- Instrument Safety Factor(ISF) ofCT
- Magnetization Curve of CT
- PS Class CT Specifications & its applications
- CT Ratio Calculator
Thanks for the post. It helped me understand what the accuracy class of a CT is and why it is used.
well done,i am happy to read it. I appreciate your website
Thanks for the valued information. I have learnt greatly from this vital information
U r writing technically sound Contents. Power engineers can understand a lot from ur work…
Hats off to ur team and keep going….
Thanks a lot
Nice content and elaboration sir